VFD rated power

For motor power

Rated voltage

Rated frequency

Modulation technique

Control power

Input power factor

Efficiency

Output frequency range

Frequency resolution

Instantaneous over-current protection

Overload capability

Current limited protection

Analog input

Analog output

Host communication


Acceleration and deceleration time

DI / DO

Environment temperature

Storage / transportation temperature

Cooling

Humidity

Altitude

Dust

Protection level

Cabinet colors
210 – 28, 000 kVA

150 – 25, 000 kW

2.3 – 13.8kV (-15% - +10%)

50 Hz / 60 Hz (-10% – +10%)

SVPWM

400 V, ≤30 kVA (dependent on power level)

>0.96

>96% (>98% for Power Electronic Part)

0 Hz – 80 Hz

0.01 Hz / 0 .002 Hz

200% protect immediately

120% ,125 s

10%-150% (1 000 ms – 3 s inverse time protection)

3 × AI with 4 – 20mA / 2 – 10V

4 × AO with 4 – 20mA

Isolated RS485 interface, ModBus RTU,
Profibus DP(optional), Industry Ethernet Protocol (optional)

5 s – 1 600 s (related to load)

14 inputs / 22 outputs

-5 – +45°C

-40 – +70°C

forced air cooling / water cooling

<95%, no condensation

<1,500m (1% derating each 100 meter above 1000 m)

Non-conductive, no causticity, <6.5 mg / dm3

IP30

RAL 7 035 (other on request)