Mains Supply
Mains voltage (L1, L2, L3)
CSXi-xxx-V4
CSXi-xxx-V6
Mains frequency (at start)
Rated insulation voltage
Form designation
Control Voltage (A1, A2, A3)
CSXi-xxx-xx-C1
CSXi-xxx-xx-C2
Current consumption (during run)
Current consumption (at power-up)
CSXi-xxx-xx-C1
CSXi-xxx-xx-C2
Inputs
Start (terminal 01)
Stop (terminal 02)
Outputs
Main contactor (terminals 13, 14)
Programmable relay (terminals 23, 24)
Environmental
Degree of protection CSXi-007 to CSX-055
Degree of protection CSXi-075 to CSX-110
Operating temperatures
Humidity
Pollution degree
Vibration
EMC Emission
Equipment class (EMC)
Conducted radio frequency emission
Radiated radio frequency emission
EMC Immunity
Electrostatic discharge
Radio frequency electromagnetic field
Rated impulse withstand voltage (Fast transients 5/50 ns)
Voltage dip and short time interruption
Harmonics and distortion
Short Circuit
Rated short-circuit current CSX-007 to CSX-037
Rated short-circuit current CSX-045 to CSX-110
Heat Dissipation
During Start
During Run
Approvals
RCM
CE
CCC
EAC
Marine
UL / C-UL
3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
45 Hz to 66 Hz
600 VAC
Bypassed semiconductor motor starter form 1
110-240 VAC (+ 10% / - 15%)
or 380-440 VAC (+ 10% / - 15%)
24 VAC/VDC (± 20%)
< 100 mA
Current consumption (at power-up)
10 A
2 A
Normally Open
150 kΩ @ 300 VAC and 5.6 kΩ @ 24 VAC/VDC
Normally Closed
150 kΩ @ 300 VAC and 5.6 kΩ @ 24 VAC/VDC
Normally Open
6 A, 30 VDC / 6 A, 250 VAC resistive
Normally Open
6 A, 30 VDC / 6 A, 250 VAC resistive
IP20
IP00
- 10 °C to + 60 °C
5% to 95% Relative Humidity
Pollution Degree 3
IEC 60068 Test Fc Sinusoidal
4 Hz to 13.2 Hz: ± 1 mm displacement
13.2 Hz to 200 Hz: ± 0.7 g
Class B
0.15 MHz to 0.5 MHz: < 56-46 dB (µV)
0.5 MHz to 5 MHz: < 46 dB (µV)
5 MHz to 30 MHz: 50 dB (µV)
30 MHz to 230 MHz: < 30 dB (µV/m)
230 MHz to 1000 MHz: < 37 dB (µV/m)
4 kV contact discharge, 8 kV air discharge
0.15 MHz to 1000 MHz: 140 dB (µV)
2 kV line to earth, 1 kV line to line
100 ms (at 40% nominal voltage)
IEC61000-2-4 (Class 3), EN/IEC61800-3
5 kA
10 kA
3 watts / ampere
atts typical
IEC 60947-4-2
EN 60947-4-2
GB 14048.6
TP TC 004/2011, TP TC 020/2011
Lloyds Marine No 1 Specification
UL 508